5 Sysmac Studio Settings for the EtherNet/IP Unit
5-12
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Trap 1
*1
Trap 2
*1
*1
These settings are required if the SNMP trap is set is enabled.
*2
Due to Ethernet restrictions, you cannot specify the IP addresses that are described below.
•
IP addresses that start with 127, 0, or 255 (decimal)
•
Class-D IP addresses (224.0.0.0 to 239.255.255.255)
•
Class-E IP addresses (240.0.0.0 to 255.255.255.255)
Setting
Description
Default
Specifying method
Set the specifying method for the SNMP manager destination for SNMP
traps.
•
IP address
•
Host name
IP address
IP address
*2
Set the IP address of the SNMP manager.
(Set this setting if the specifying method in the trap 1 settings is set to the IP
address Option.)
0.0.0.0
Host name
Set the host name of the SNMP manager.
(Set this setting if the specifying method in the trap 1 settings is set to the
Host name Option.)
(You can use up to 200 single-byte alphanumeric characters, dots, and
hyphens with up to 63 single-byte alphanumeric characters between dots.)
None
Community name
Set the community name.
(You can use up to 200 alphanumeric characters.)
public
Version
Set the version of the SNMP manager.
•
SNMPv1
•
SNMPv2C
SNMPv2C
Setting
Description
Default
Specifying method
Set the specifying method for the SNMP manager destination for SNMP
traps.
•
IP address
•
Host name
IP address
IP address
*2
Set the IP address of the SNMP manager.
(Set this setting if the specifying method in the trap 2 settings is set to the IP
address Option.)
0.0.0.0
Host name
Set the host name of the SNMP manager.
(Set this setting if the specifying method in the trap 2 settings is set to the
Host name Option.)
(You can use up to 200 single-byte alphanumeric characters, dots, and
hyphens with up to 63 single-byte alphanumeric characters between dots.)
None
Community name
Set the community name.
(You can use up to 200 alphanumeric characters.)
public
Version
Set the version of the SNMP manager.
•
SNMPv1
•
SNMPv2C
SNMPv2C
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......