3 Assigning Device Variables for CJ-series Units
3-18
CJ-series EtherNet/IP Units Operation Manual for NJ-series CPU Unit (W495)
Information is stored for nodes 0 to 255.
This variable is a union, which allows access with different data types.
You can specify different data types to access the data: a BOOL array variable with 256 elements,
256 BOOL variables, or WORD variables.
This variable gives the registration status of the target nodes. It is valid only when the EtherNet/IP Unit
is the originator of the connection.
x.RegTargetSta.TargetSta [0] to [255]
x. RegTargetSta.TargetStaWd [0] to [15]
x: The name of the user-defined variable that is specified for the status area in the user settings.
This variable gives the connection status of the target nodes. The elements of this variable change to
TRUE after all data for multiple connections for individual target devices is refreshed in the CPU Unit.
x.EstbTargetSta.TargetSta [0] to [255]
x. EstbTargetSta.TargetStaWd [0] to [15]
x: The name of the user-defined variable that is specified for the status area in the user settings.
Structure data type name
Member
Data type
_uCJEIP21_TargetSta
TargetSta
array[0..255] of BOOL
TargetStaWd
array[0..15] of WORD
3-3-4
Status Information Assigned to the User-defined Area
Registered Target Node Table (EtherNet/IP Unit to CPU Unit)
Bit
Meaning
Status
Manipulated
by
Unit operation
Reference
---
Registered Target
Node Table
TRUE
EtherNet/IP
Unit
The tag data links are registered.
3-2-3 Device Vari-
ables for the CJ-
series Unit for Status
FALSE
EtherNet/IP
Unit
The tag data links are not registered.
Normal Target Node Table (EtherNet/IP Unit to CPU Unit)
Bit
Meaning
Status
Manipulated
by
Unit operation
Reference
---
Normal Target
Node Table
TRUE
EtherNet/IP
Unit
The corresponding element changes to
TRUE after all data for multiple connec-
tions for the target device is refreshed in
the CPU Unit.
3-2-3 Device Vari-
ables for the CJ-
series Unit for Status
FALSE
EtherNet/IP
Unit
Other than the above.
Summary of Contents for SYSMAC CJ1W-EIP21
Page 8: ...Manual Structure 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 42: ...Revision History 40 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 68: ...1 Introduction 1 26 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 266: ...9 FTP Server 9 20 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495...
Page 431: ...Index 1 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 I Index...
Page 436: ...Index 6 CJ series EtherNet IP Units Operation Manual for NJ series CPU Unit W495 Index...
Page 437: ......