74
Other Errors
Section 6-4
6-4
Other Errors
0376
Slave duplication error
Cause:
A Slave duplication error
occurred.
0x80:
Slice I/O
Node address
(Hex)
No
Verify that the Unit is con-
nected properly and turn the
power ON again.
0378
I/O size error
0x00
0x00
No
Verify that the Unit is con-
nected properly and turn the
power ON again.
0379
Slice configuration error
0x00
0x00
No
Verify that the Unit is con-
nected properly and turn the
power ON again.
Status
Likely cause and remedy
The Communications Unit’s
Unit Power indicator is flash-
ing.
The Unit power supply capacity is insufficient. Check the entire Slice I/O Terminal’s power
supply requirement and replace the power supply with one that has sufficient capacity.
The Communications Unit
repeatedly checks indicators
(MS/NS indicator flashing
green and red).
The I/O Unit repeatedly
checks indicators (TS indica-
tor flashing green and red).
The Unit power supply capacity is insufficient. Check the entire Slice I/O Terminal’s power
supply requirement and replace the power supply with one that has sufficient capacity.
The Communications Unit’s
TS indicator flashes green.
The I/O Unit’s indicator in front
of the bad connection lights
green and the indicator
behind the bad connection
goes OFF.
The slide connector on the left side of the affected Unit is not connected properly. Connect
this slide connector properly and turn the power ON again.
The Communications Unit’s
TS indicator flashes green
and the I/O Unit’s TS indicator
flashes green.
The End Unit is not connected properly. Connect the End Unit properly and turn the power
ON again.
After the Communications
Unit’s MS indicator lights
green, NS indicator lights red
immediately, without flashing.
Check the following items and restart the problem Slave.
• A node address is duplicated.
Check all of the node addresses and set them again to eliminate the duplication.
• Check whether the baud rates match on the Master and all Slaves.
If there are any Slaves with different baud rates, set them to the same baud rate.
• See the troubleshooting steps below under the error heading “The NS indicator lights
green but changes to red after a short time.”
• If a particular Slave's NS indicator is always red, replace that Slave.
Error
code
(Hex)
Contents
Details
Saved in error
history when
power goes OFF?
Corrective action
1st byte
2nd byte
Communications
Unit Indicator
I/O Unit Indicator
Bad connection
Not lit (OFF)
LED Indicator
Communications
Unit Indicator
I/O Unit Indicator
Bad connection
End Unit
LED Indicators
Summary of Contents for SMARTSLICE - 04-2008
Page 1: ...DeviceNet Communications Unit Cat No W454 E1 03 SmartSlice GRT1 DRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 DRT DeviceNet Communications Unit Operation Manual Revised April 2008 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 27: ...8 Basic Operating Procedure Section 1 5 ...
Page 57: ...38 Unit Functions Section 2 3 ...
Page 101: ...82 DeviceNet Explicit Messages Appendix A ...
Page 113: ...94 Standard Models Appendix C ...
Page 115: ...96 Power Consumption Tables Appendix D ...
Page 117: ...98 I O Current Consumption Appendix E ...
Page 119: ...100 Glossary ...