Troubleshooting Overview
Section 6-1
6-1
Troubleshooting Overview
6-1-1
Checking the Slice I/O Terminal’s Status
The following two methods can be used to check for Slice I/O Terminal errors.
Use the appropriate method for the conditions.
6-1-2
LED Indicators
The following LED indicators in the Slice I/O Terminal show the system status.
The Slice I/O Terminal is operating normally when all of the LED indicators
are lit green (including indicators on the DeviceNet Communications Unit,
Slice I/O Units, Turnback Units, etc.).
6-2
LED Indicators and Error Processing
The following table shows the meaning of the LED indicators on each Unit
used in a Slice I/O Terminal, as well as error processing required when an
error is indicated.
Method
Programming
Device
Features
Using LED indicators Not required.
The general error status can be determined
without using the DeviceNet Configurator.
Using DeviceNet
Configurator
Required.
The DeviceNet Configurator can be used to
find detailed information about the error
from the error contents.
MS LED: Indicates the status of the DeviceNet Communications Unit.
NS LED: Indicates the status of DeviceNet communications.
TS LED: Indicates the status of the entire Slice I/O Terminal.
UNIT PWR: Indicates the status of the Unit power supply.
I/O PWR: Indicates the status of the I/O power supply.
TS LEDs: Indicate the status of each Slice I/O Unit.
Unit
LED
name
Color
Status
Meaning
Likely cause of error
DeviceNet
Communica-
tions Unit
MS
Green
Unit operating normally.
---
---
Power is not being supplied to
the Unit.
Check whether power is being supplied by
the Unit power supply.
Red
Unit hardware failure
Turn the power OFF and then ON again.
Replace the Unit if the error recurs.
Red
Parameter data is invalid.
Use a Programming Device to write the cor-
rect data again.
Backup data is invalid.
Backup the data again.
Registration table data is
invalid.
Register the I/O configuration table again.
MS
MS
MS
MS
Summary of Contents for SMARTSLICE - 04-2008
Page 1: ...DeviceNet Communications Unit Cat No W454 E1 03 SmartSlice GRT1 DRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 DRT DeviceNet Communications Unit Operation Manual Revised April 2008 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 27: ...8 Basic Operating Procedure Section 1 5 ...
Page 57: ...38 Unit Functions Section 2 3 ...
Page 101: ...82 DeviceNet Explicit Messages Appendix A ...
Page 113: ...94 Standard Models Appendix C ...
Page 115: ...96 Power Consumption Tables Appendix D ...
Page 117: ...98 I O Current Consumption Appendix E ...
Page 119: ...100 Glossary ...