
70
LED Indicators and Error Processing
Section 6-2
DeviceNet
Communica-
tions Unit,
continued
TS
Green
The Slice bus is operating
normally.
---
---
Power is not being supplied to
the Unit.
Check whether power is being supplied by
the Unit power supply.
Red
Slice I/O Unit configuration
error occurred.
Check the following items.
• Are more than 64 I/O Units connected?
• Are more than 128 bytes of I/O data being
used?
• Has the I/O configuration changed since
the I/O configuration table was registered?
Red
(for 2 s)
Backup operation failed.
Backup the data again.
Restore operation failed.
Reinstall the Unit in which the data was
being restored and turn the power ON
again.
Red
Slice bus communications
error occurred.
Check whether the Slice I/O Terminal’s
base block is connected properly.
When the registration table
function is enabled, the actual
configuration does not match
the registered configuration.
Correct the configuration and turn the
power ON again.
Green
The total number of I/O points
in the Slice I/O Terminals
exceeds the maximum.
Correct the Unit configuration and number
of I/O points and turn the power ON again.
Restore operation in progress Wait until the restore operation is com-
pleted.
Backup operation in progress
Wait until the backup operation is com-
pleted.
Joining nodes to network
Wait until the nodes have been added to the
network.
UNIT
PWR
Green
Unit power supply is providing
power normally.
---
---
Unit power supply is not being
supplied to the Unit.
Check whether power is being supplied by
the Unit power supply.
IO
PWR
Green
I/O power supply is providing
power normally.
---
---
I/O power supply is not being
supplied to the Unit.
Check whether power is being supplied by
the I/O power supply.
Slice I/O Units TS
Green
Slice I/O Unit operating nor-
mally.
---
---
Unit power supply is not being
supplied to the Unit.
Check whether power is being supplied by
the Unit power supply.
Red
Unit hardware failure
Turn the power OFF and then ON again.
Replace the Unit if the error recurs.
Communications error
occurred.
Check whether the connector is inserted
properly.
Green
Restore operation in progress Wait until the restore operation is com-
pleted.
Backup operation in progress
Wait until the backup operation is com-
pleted.
GRT1-PD2
I/O Power
Supply Unit
IO
PWR
Green
I/O power supply is providing
power normally.
---
---
I/O power supply is not being
supplied to the Unit.
Check whether power is being supplied by
the I/O power supply.
Unit
LED
name
Color
Status
Meaning
Likely cause of error
TS
TS
TS
TS
NS
NS
TS
TS
TS
TS
TS
Summary of Contents for SMARTSLICE - 04-2008
Page 1: ...DeviceNet Communications Unit Cat No W454 E1 03 SmartSlice GRT1 DRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 DRT DeviceNet Communications Unit Operation Manual Revised April 2008 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 27: ...8 Basic Operating Procedure Section 1 5 ...
Page 57: ...38 Unit Functions Section 2 3 ...
Page 101: ...82 DeviceNet Explicit Messages Appendix A ...
Page 113: ...94 Standard Models Appendix C ...
Page 115: ...96 Power Consumption Tables Appendix D ...
Page 117: ...98 I O Current Consumption Appendix E ...
Page 119: ...100 Glossary ...