18
Node Address Settings and I/O Allocation
Section 2-2
Allocated Data Size
Note
When allocating data, be sure that it does not exceed the maximum that can
be allocated (64 words).
Status Flags
The status flags can be allocated in the Master independently or together with
the I/O data. There are two kinds of status flags, the Communications Unit’s
status flags and I/O Units’ communications participating/withdrawn flags, and
these status flags must be allocated in separate areas.
Communications Unit’s
Status Flags
These flags can be used to monitor the status of the connection with the Mas-
ter and the status of Slice I/O Units connected to the Communications Unit.
The status flags take up 2 words and the information is transferred to the Mas-
ter.
With the default data pattern (pattern 1), these status flags are allocated in the
Master together with the I/O data. The status flags can also be read with the
Configurator or an explicit message command.
Data type
Data size
I/O data (input and output)
When only the actual I/O data is allocated:
64 input words max. or 64 output words max.
The GRT1-ID4(-1) and GRT1-OD4(-1) use 4 bits
per Unit.
The GRT1-ROS2 uses 2 bits.
Communications Unit status flags
1 word
Slice I/O Unit communications
participating/withdrawn flags
Participating flags: 4 words
Withdrawn flags: 4 words
Total: 8 words
I/O data (inputs) + Communica-
tions Unit status flags
Amount of I/O data being used + 1 word
Bit
Content
Description
0
Slice I/O Bus Communications Error Flag
Monitors the status of Slice I/O Terminal communications.
1
Reserved
---
2
Slice I/O Unit Warning Flag
0: Normal; 1: Error detected
Indicates a major Slice I/O Unit error. This flag goes ON when
there is an error in any one of the connected Slice I/O Units.
3
Reserved
---
4
Slice I/O Unit Alarm Flag
0: Normal; 1: Error detected
Indicates a minor Slice I/O Unit error. This flag goes ON when
there is an error in any one of the connected Slice I/O Units.
Status flags (16 bits)
Master CPU Unit
DeviceNet
Communications Unit
First word
I/O data (4 bits)
Status flags
Slice I/O Unit (4 inputs)
Input Area
Summary of Contents for SMARTSLICE - 04-2008
Page 1: ...DeviceNet Communications Unit Cat No W454 E1 03 SmartSlice GRT1 DRT OPERATION MANUAL ...
Page 2: ...SmartSlice GRT1 DRT DeviceNet Communications Unit Operation Manual Revised April 2008 ...
Page 3: ...iv ...
Page 5: ...vi ...
Page 13: ...xiv ...
Page 27: ...8 Basic Operating Procedure Section 1 5 ...
Page 57: ...38 Unit Functions Section 2 3 ...
Page 101: ...82 DeviceNet Explicit Messages Appendix A ...
Page 113: ...94 Standard Models Appendix C ...
Page 115: ...96 Power Consumption Tables Appendix D ...
Page 117: ...98 I O Current Consumption Appendix E ...
Page 119: ...100 Glossary ...