5-56
5-10 User Parameters
5
Operating Functions
Set the number of rotations for the Servomotor Rotation Speed Detection Output (TGON) during
Internally Set Speed Control.
The Servomotor Rotation Speed Detection Output (TGON) will turn ON if the Servomotor speed
exceeds the set speed regardless of the direction of rotation.
There is a hysteresis of 10 r/min, so set a value higher than 10.
Set the detection level for the deviation counter overflow alarm.
The alarm level is the setting value multiplied by 256 pulses.
The deviation counter overflow alarm can be disabled so that it does not occur.
Explanation of Settings
Pn62
Rotation Speed for Servomotor Rotation Detection
Setting range
0 to 20000
Unit
r/min
Default setting
50
Power OFF
→
ON
---
Internally set speed
Speed
Reverse
TGON
Forward
Pn62
Pn62
Pn63
Deviation Counter Overflow Level
Setting range
0 to 32767
Unit
×
256 pulses
Default setting
100
Power OFF
→
ON
---
Position
Pn64
Deviation Counter Overflow Alarm Disabled
Setting range
0 or 1
Unit
---
Default setting
0
Power OFF
→
ON
---
Position
Setting
Explanation
0
Enabled
1
Disabled
Pn65
Not used. (Do not change setting.)