3 Initial Setting
3 - 8
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
When using Ethernet for the first time, if you set the IP address and subnet mask of the computer and
Main Unit as below, it is possible to connect the software tool to the Main Unit.
When the subnet mask is "255.255.255.0", the range of IP addresses that can be set for the devices
192.168.250.1 to 192.168.250.254. Assign IP address in this range to each Main Unit.
The same IP address can not be assigned to more than one device.
The default value of the IP address of type Main Unit is “192.168.250.30” common to all models.
IP Address Settings Example
Device name
IP address
Sub-net mask
Default gateway
Computer
192.168.250.100
255.255.255.0
Blank
Main Unit 1st Unit
192.168.250.1
255.255.255.0
No change required
(0.0.0.0)
Main Unit 2nd Unit
192.168.250.2
255.255.255.0
No change required
(0.0.0.0)
Main Unit 3rd Unit
192.168.250.3
255.255.255.0
No change required
(0.0.0.0)
:
:
:
:
Main Unit 30th Unit
192.168.250.30
255.255.255.0
No change required
(0.0.0.0)
When subnet mask set for the all devices is "255.255.255.0",
each of devices having an IP address within the range of 192.168.250.1 to 192.168.250.254
can communicate via Ethernet as the devices are to exist on the same network (segment).
Network of 192.168.249.×××
IP address: 192.168.249.1
Network of 192.168.250.×××
Main Unit
IP address: 192.168.249.1
Main Unit
IP address of your PC:
192.168.250.100
Ethernet communications
can be performed because
the Main Units are in the
same network.
Ethernet communica-
tions can not be
performed because
the Main Units are in
a different network.
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......