7 Troubleshooting
7 - 2
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
7-1
Main Unit
This section shows how to troubleshoot the Main Units.
If the Main Unit does not operate properly, check the items below as required before repair is
requested. If it still does not work properly, return it through our sales department.
Troubleshooting
Problems
Cause
Possible correction
Reference
Measure-
ment val-
ues are
not dis-
played.
"
----
" dis-
played
This is the state
before the estab-
lishment of com-
munications with
the sensor.
(From after the
power supply is
turned ON or the
software is reset
until the initial mea-
surement value is
calculated)
Wait until communications is
established with all connected
sensors. It takes a maximum of
approximately 30 seconds for
communications to be estab-
lished.
---
"
serr
" is dis-
played.
The sensor is not
properly con-
nected and
installed.
• Check the power supply to the
sensor.
• Check the communications wir-
ing with the sensor.
• Check the terminating resis-
tance (by the DIP switch pin) of
the sensor.
• Turn ON the power supply to
the sensor again.
• If no improvement is seen after
taking the above action,
replace the sensor.
"
8888
" lights
up.
The Main Unit may
be damaged.
Turn ON the power supply to the
Main Unit again. If it still occurs,
contact our sales or distributor.
---
The current
temperature is
displayed, but
MS blinks red
and K6PM sen-
sor error is ON
in the K6PM
device status.
A K6PM-TH sensor
error has occurred.
One of the follow-
ing.
• K6PM-TH sen-
sor communica-
tions error
• The detection of
the K6PM-TH
sensor angle
deviation
• Temperature
measurement
range exceeded
• Check the power supply to the
sensor.
• Check the communications wir-
ing with the sensor.
• Check the terminating resis-
tance (by the DIP switch pin) of
the sensor.
• Return the sensor angle to its
original state.
• Alternatively, perform position
adjustment and position regis-
tration.
• Make sure there is no error in
the measurement object.
1-9
Refer to the Product
and Network Status
Indications Details.
Refer to
Take When Angle Devi-
ation Occurs
7-5 described later.
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......