![background image](http://html1.mh-extra.com/html/omron/k6pm-th/k6pm-th_user-manual_743374123.webp)
5 - 21
5 Monitoring and Setting with the EtherNet/IP Communications
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
5-3
Monit
o
rin
g
an
d Sett
ing
Usin
g th
e CIP
Messag
e Com
m
u
n
icat
ion
s and
Exam-
p
les o
f Co
mm
unic
ation
s In
struct
ion
s
5
5-
3-6 K6PM-
T
H Sensor
Alarm Setting Obje
ct (
C
la
ss ID: 378
hex)
67 hex
K6PM-TH sensor 1 seg-
ment 0
Current temperature alarm
setting (threshold 2)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
03E8 hex
(100.0)
68 hex
K6PM-TH sensor 1 seg-
ment 0
Differential temperature
alarm setting (threshold 1)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
012C hex
(30.0)
69 hex
K6PM-TH sensor 1 seg-
ment 0
Differential temperature
alarm setting (threshold 2)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
01C2 hex
(45.0)
6A hex
K6PM-TH sensor 1 seg-
ment 1
Current temperature alarm
setting (threshold 1)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
02BC hex
(70.0)
6B hex
K6PM-TH sensor 1 seg-
ment 1
Current temperature alarm
setting (threshold 2)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
03E8 hex
(100.0)
6C hex
K6PM-TH sensor 1 seg-
ment 1
Differential temperature
alarm setting (threshold 1)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
012C hex
(30.0)
6D hex
K6PM-TH sensor 1 seg-
ment 1
Differential temperature
alarm setting (threshold 2)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
01C2 hex
(45.0)
:
:
:
:
:
:
A2 hex
K6PM-TH sensor 1 seg-
ment 15
Current temperature alarm
setting (threshold 1)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
02BC hex
(70.0)
A3 hex
K6PM-TH sensor 1 seg-
ment 15
Current temperature alarm
setting (threshold 2)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
03E8 hex
(100.0)
A4 hex
K6PM-TH sensor 1 seg-
ment 15
Differential temperature
alarm setting (threshold 1)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
012C hex
(30.0)
A5 hex
K6PM-TH sensor 1 seg-
ment 15
Differential temperature
alarm setting (threshold 2)
(0000 to 270F hex)
(0 to 999.9 (unit: °C/°F))
Write
UINT
01C2 hex
(45.0)
Attribute ID
Parameter name
Description
Attribute
Data
Data type
Default
value
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......