5 Monitoring and Setting with the EtherNet/IP Communications
5 - 26
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
Attribute
ID
Parameter name
Description
Attribute
Data
Data type
Default value
03 hex
Configuration Control
Sets the method used to set
the IP address when the
interface starts.
0: Static IP address.
1: Set by BOOTP.
Write
DWORD
00000000 hex
04 hex
Physical Link Object
The path to the link object in
the physical layer
Read
Struct of
- - -
Path size
The path size (WORD size).
UINT
0002 hex
Path
The path to the link object in
the physical layer
(Path to the Ethernet Link
object (Class ID: F6 hex))
Padded
EPATH
20F6 2401 hex
05 hex
Interface Configuration
Interface settings
Write
Struct of
- - -
IP Address
IP address
UDINT
Set value (Fac-
tory default:
192.168.250.30)
Network Mask
Subnet mask.
UDINT
255.255.255.0
Gateway Address
The default gateway.
UDINT
0.0.0.0
Name Server
The primary name server.
UDINT
0.0.0.0
Nana Server2
The secondary name server.
UDINT
0.0.0.0
Domain Name
The domain name.
STRING
0000 hex. (fixed)
06 hex
Host Name
The host name (reserved).
*1
*1. Only the Host Name immediately reflects the change in settings. (It is not necessary to reset the power supply
to apply the changes in the setting parameters to the operation)
Write
STRING
0000 hex. (fixed)
0D hex
Encapsulation Inactiv-
ity Timeout
Encapsulation session time-
out time
(Timeout time of TCP con-
nection or DLTS connection)
Write
UINT
0078 hex (120
seconds)
Setting range: 1
to 3,600 seconds
(0: Prohibited)
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......