5 - 5
5 Monitoring and Setting with the EtherNet/IP Communications
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
5
-2 Mo
nito
ring
Using
th
e T
ag
Dat
a Lin
k
5
5-
2-1 C
onnection Setting
• The size of the internal data (parameter) of the K6PM device must be any one of 128 bytes,
380 bytes, and 418 bytes.
2)-1 Drag a K6PM-TH to the PLC and register it.
2)-2 Click the
Edit Tag Sets
Button to create input tags with the above sizes.
2)-3 Register the input tag as it is as input tag set.
2)-4 Select the input tag set created in 2)-3 above from the pull-down list.
2)-5 Match the connection I/O type and instance ID of the output tag set.
2)-6 Register the connection.
Connection Allocation to K6PM Device
Dialog Box
PLC side tag set
K6PM side tag set
This size is any one of
128 bytes, 380 bytes,
and 418 bytes.
Output tag set
Input tag set
PLC
K6PM-TH
Select any one of the tag sets of
128 bytes, 380 bytes, and 418
bytes that you have created.
Create a tag that matches any one of
the sizes of 128 bytes, 380 bytes, and
418 bytes of the internal data of the
K6PM device selected on the right, and
set it as the input tag set as it is.
Select the output tag set name to be
displayed from below.
• "Input_100-[128Bytes]"
• "Input_101-[380Bytes]"
• "Input_102-[380Bytes]"
• "Input_103-[418Bytes]"
Match the connection
I/O type and instance ID
of the output tag set.
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......