![background image](http://html1.mh-extra.com/html/omron/k6pm-th/k6pm-th_user-manual_743374028.webp)
1 Outline
1 - 10
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
(D)
Numeric LCD display
Depending on the operating mode, the display differs as shown
below.
• Monitoring mode: Current temperature of the selected segment of
the selected sensor
(a) When communications are not established with the sensor:
"
----
" is displayed
(b) When a K6PM-TH sensor communications error occurs:
"
serr
" is displayed
(c) When the sensor temperature exceeds the measurement
range: The current temperature flashes
(d) During measurement interruption due to an external trigger:
The display is fixed as the value immediately before interrup-
tion
(e) K6PM-TH sensor search mode: "
on
" is displayed for a sensor
that sends a response, and "
off
" is displayed for a sensor that
sends no response
• K6PM-TH sensor position adjustment mode: "
adj
" is displayed
• When a Main Unit internal error occurs: "
8888
" flashes
(E)
SEG
The segment number or the number of currently-connected infrared
thermal sensors is displayed. Depending on the operating mode, the
display differs as shown below.
• Monitoring mode: The segment number selected by the
SEG/ALM
RST
Key is displayed. 0 to 15 Sensor internal temperature: 99
• K6PM-TH sensor search mode: The number of infrared thermal
sensors currently connected to the Main Unit is displayed.
• K6PM-TH sensor position adjustment mode: The number of infra-
red thermal sensors currently connected to the Main Unit is dis-
played.
(F)
Status display
The status of the Main Unit is displayed as follows:
• MON: K6PM-TH sensor monitoring state. The indicator is not lit
during measurement interruption due to an external trigger.
• ALM: Alarm occurrence state (lit only when the corresponding
K6PM-TH sensor number is being displayed)
• AGE: Running time reaches 100%
• ERR: Main Unit internal error
(G)
Operation Keys
CH
Key: Switching of sensor number
SEG/ALM RST
Key pressed for less than 5 seconds: Switching of
segment number
SEG/ALM RST
Key pressed and held (5 seconds min.): Alarm latch
released (Can be performed only by this operation. The latch cannot
be released by the software tool and communications.)
CH
Key and
SEG/ALM RST
Key simultaneously pressed and held (5
seconds min.): Initialization
(Operation returns to the factory state.)
(H)
Lower terminal
Connection is established by the Push-In Plus terminal.
• Transistor output 1 to 3
For details, refer to
(I)
DIN Track mounting hook
Used for mounting to the DIN Track.
(J)
Communications connec-
tor
Connects the communications cable of the EtherNet/IP network.
Symbol
Name
Function
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......