A - 5
Appendices
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
A-
1 Spec
ificat
ions
A
A-1-
1 Main Unit Specifications
Transistor Output Specifications
NS
Net-
work
Status
Green
Lit
Tag data link or message connection established
Flashes at 1-s
intervals
No tag data link or message connection established
Red
Lit.
IP address duplication status
Flashes at 1-s
intervals
The connection has timed out
---
Not lit
No power supply, or IP address not set
Name
Description
Transistor
Output 1
Threshold 1 excess output of comprehensive alarm.
If threshold 1 exceeded occurs for the
comprehensive alarm, transistor output 1
remains OFF and transistor output 2
remains ON.
If threshold 2 exceeded occurs for the
comprehensive alarm, both transistor out-
put 1 and transistor output 2 turn OFF.
(Normally closed type)
Transistor output type can be set to Normally Closed or
Normally Open.
Transistor
output 2
Threshold 2 excess output of comprehensive alarm.
Transistor output type can be set to Normally Closed or
Normally Open.
Transistor
output 3
Main Unit error and K6PM-TH sensor error output
*1
• Normal: ON
• Main Unit error and K6PM-TH sensor error: OFF
The output type of transistor output 3 is fixed as Nor-
mally closed.
*1. The Main Unit error and K6PM-TH sensor error specify any one of the following:
• Main Unit internal error (internal CPU error or internal memory error)
• K6PM-TH sensor communications error or sensor type error
• The detection of the K6PM-TH sensor angle deviation
• Temperature measurement range exceeded
• Running time error
*2
*2. The operation of transistor output 3 is as described below.
Status
Transistor
output 3
Status of Main Unit
Status of infrared thermal sensor
Operating
OFF
Main Unit internal error
In monitoring mode
Before data acquisition
ON
Normal
K6PM-TH sensor communications error or sensor type
error
OFF
The detection of the K6PM-TH sensor angle deviation
Temperature measurement range exceeded
Running time error
K6PM-TH sensor search mode or
K6PM-TH sensor position adjust-
ment mode
Before data acquisition
ON
Normal
K6PM-TH sensor communications error or sensor type
error
The detection of the K6PM-TH sensor angle deviation
Temperature measurement range exceeded
Running time error
OFF
Symbol
Name
Color
Status
Operating condition
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......