Appendices
A - 8
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
Infrared Thermal Sensor Characteristics
Model
K6PM-THS3232
Item
Temperature
measurement
Temperature mea-
surement range
Temperature measurement range: 0.0°C to 200.0°C (32.0°F to 392.0°F)
Detection resolu-
tion
32 × 32 (1,024 pixels)
Temperature accu-
racy
±5°C (at an ambient temperature of 25°C)
*1*2
*1. Accuracy may vary depending on the measured distance, the object's emissivity, and ambient temperature.
*2. Accuracy for the central four segments when the measured object is 25°C to 80°C. If a high temperature object
is measured with the outer 12 segments, the accuracy may decrease due to area effect.
Emissivity
0.94
Reproducibility
±1°C (at an ambient temperature of 25°C)
*3
*3. Performance of central four segments. ±2°C for the outer 12 segments.
Temperature drift
0.15°C
Warm up time
15 minutes
Viewing angle
[FOV]
90° × 90°
Other functions Temperature mea-
surement range
exceeded
Outputs K6PM-TH sensor error in following condition
Temperature: 200.0°C or higher
Sensor internal temperature: 80°C or higher
Angle deviation
detection
*4
*4. Make ON/OFF settings on the DIP switch Pin 2 (default value: OFF). For details, refer to
Detection of only angle deviation
*5
*5. Since the operation is not stable at a location subject to vibrations, it may not be possible to detect angle de-
viation.
Angle deviations of 5° (typ) min. and those that continue for 3 seconds
min. can be detected.
Output
Communications
method
RS-485 communications
Maximum cable
length
500 m
Applicable
standards
Approved stan-
dards
UL61010-1 (listing) installation location: Pollution degree 2
Korean Radio Waves Act
Conforming stan-
dards
RCM
EMC
EN61326-1 (EMI: Class A EMS: Industrial Location), Measured tempera-
ture fluctuation range: ±6°C
Recommended fuse
T2A, time lag, shut-off capacity
Insulation resistance
20 M
Ω
min.
Between all terminals and the case
Dielectric strength
1,000 VAC for 1 minute
Between all terminals and the case
Vibration resistance
Frequency: 10 to 55 Hz, 0.35-mm single amplitude in X, Y, and Z direc-
tions (10 sweeps of 5 min each)
*6
*6. During screw mounting
Shock resistance
150 m/s
2
, 3 times each in 6 directions along 3 axes
*6
Degree of protection
IP20
Indicators
Power indicator
Green (when power is on: Lit, when power is not on: Not lit)
Communications
indicator
Orange (when communications are performed: Lit, when communica-
tions are not performed: Not lit)
Alarm indicator
Red (when a sensor error occurs: Lit, when an angle deviation is
detected: Flashing)
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......