Appendices
A - 4
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
Indicator Specifications
Model
K6PM-THMD-EIP
Item
Ethernet
communi-
cations
Supported services
EtherNet/IP (tag data link or CIP message com-
munications)
BOOTP client
Modbus TCP
Physical layer
100Base-TX
Transmis-
sion specifi-
cations
Transmission speed
100 Mbps
Transmission medium
Twisted pair cable (with shield: STP): Category
5 or higher
Transmission distance
100 m max. (distance between hub and node)
Tag data
link
*1
*1. When you use tag data link, explicit message communications, and Modbus message communications simul-
taneously, limit the number of client nodes to 4 or less. If simultaneous communication is carried out with 5 or
more nodes, a timeout may occur due to the communications load.
Class1
Connection resource: 4 max.
Packet interval (RPI)
1,000 to 10,000 ms
Timeout value
Multiples of RPI (4 times, 8 times, 16 times, 32
times, 64 times, 128 times, 256 times, 512
times)
Connection type
Point To Point Connection (fixed)
Explicit
message
*1
Class 3
Number of clients that can communicate at one
time: 2 max.
UCMM
Number of clients that can communicate at one
time: 2 max.
Modbus
message
*1
Modbus TCP
Number of clients that can communicate at one
time: 2 max.
Factory
default val-
ues
IP address
192.168.250.30
Subnet mask
255.255.255.0
Default way
0.0.0.0
IP address setting method
Static IP address
Symbol
Name
Color
Status
Operating condition
MS
Module
Status
Green
Lit
Normal status
Flashes at 1-s
intervals
BOOTP server connection error state
Red
Lit
One of the following fatal errors (Main Unit internal error)
• Internal CPU error
• Internal memory error
Flashes at 1-s
intervals
One of the following conditions
• K6PM-TH sensor communications error
• The detection of the K6PM-TH sensor angle deviation
• Sensor type error
• Temperature measurement range exceeded
• Running time error
---
Not lit
No power supply
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......