5 Monitoring and Setting with the EtherNet/IP Communications
5 - 28
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
*1. If the value of "ErrorID" is WORD#16#1C00 (Explicit error), the CIP message error code is stored in "ErrorI-
DEx". For details on "ErrorIDEx", refer to
A-4 Expansion Error Code of the CIP Message Communications
RqPath
Request path
specification
Specified by user
variable indicat-
ing the Request
path
Specify a user-defined variable.
Use the data type "_sREQUEST_PATH" cor-
responding to the input variable "RqPath".
You can use any variable name.
Specify the following.
Class ID, Instance ID, Attribute ID
Example: Reading the Main Unit status:
Specify the following.
ClassID: = 374 hex (meaning of "Main Unit
monitor object")
InstanceID: = 01 hex (fixed)
isAttributeID: = TRUE (meaning to use an
attribute ID)
AttributeID: = 64 hex (meaning of Main Unit
status)
ServiceDat
Data to send
Not used
(dummy variable)
Since the service code is "read", specify a
dummy variable.
Size
Number of ele-
ments to send
UINT#0
Since the service code is "read", specify inte-
ger 0 (fixed).
RespServiceDat
Response
data specifica-
tion
Specified by user
variable r vari-
able to receive
response data
Specify a user-defined variable.
Use the data type "ARRAY [0..10] OF BYTE"
corresponding to the input/output variable
"RespServiceDat". You can use any variable
name.
Input variable of the com-
munications instruction
Specification
Value to pass to
input variable
Meaning
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......