6 - 5
6 Monitoring and Setting with the Modbus TCP
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
6-
2 Fu
ncti
on C
ode
s
6
6-
2-3 06 h
ex: Oper
ation
Command
Software reset, K6PM-TH sensor registration, K6PM-TH sensor mode change, K6PM-TH sensor loca-
tion registration, max. temperature reset, etc. are executed.
The frame configurations of Modbus TCP are as follows.
Request
Normal Response
It is the same as the request.
Error Response
Note For the other elements (the elements shaded in the above figure), the value specified in the request is
set.
6-2-3
06 hex: Operation Command
Frame Configurations
(1): Transaction ID
Specify any value. For example, 0000 hex is used in this explanation.
(2): Protocol ID
Specify 0000 hex.
(3): Number of bytes transferred
Specify the total number of bytes of (4) and the successor. In the above
case, it is from (4) to (7), so it is 0006 hex.
(4): Unit ID
Specify FF hex.
(5): Function code
Specify 06 hex (Operation command).
(6): Start address
Specify D000 hex (Software reset).
(7): Number of words to read
Specify 0001 hex (Reset).
(3): Number of bytes transferred
The total number of bytes of (4) and the successor is set.
(5): Function code
86 hex is set.
(10): Exception code
Error information is set. Refer to
(1)
(2)
(3)
(4)
(5)
(6)
(7)
2
2
2
1
1
2
2
00
00
00
00
00
06
FF
06
←
Number of bytes
←Hex
D0
00
00
01
(1)
(2)
(3)
(4)
(5)
(10)
2
2
2
1
1
1
00
00
00
00
00
03
FF
86
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......