![background image](http://html1.mh-extra.com/html/omron/k6pm-th/k6pm-th_user-manual_743374173.webp)
A - 17
Appendices
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
A
-3 T
ag D
at
a
L
in
k
C
o
nn
ec
ti
o
n Se
tti
ng
Pro
c
ed
ur
es
A
A-3-
2 Using
the CS/CJ-series
The device names and major CIP revisions (Rev
□
) are displayed in the hardware list.
The device name and the major CIP revision of the CS/CJ-series CPU Unit are as follows.
(2) Device Node Address (IP Address) Setting
Set the node address (IP address) of the device to be used.
In the Network Configuration Window, click the device you want to change the node
address IP address), right click and select
Change Node Address (A)...
.
Enter the node address (IP address) of the device to be used actually, and click
OK
.
4
EtherNet/IP Connection Settings
The procedure of creating the tag sets and setting the connections is described below. The
internal data (parameters) of the tag data link supported by the Main Unit is assigned to any one
of the four tag sets. Therefore, it is necessary to select the tag set to use according to the pur-
pose of the customer, and then set it.
(1) Create Tag sets and Tags
Create tag sets and those members tags necessary for connection for the registered Ether-
Net/IP Unit. For tags, you can set the I/O memory address or network symbols used by the
control program (CJ2H-CPU6
□
-EIP21 and CJ2M-CPU3
□
only).
Additional Information
The setting contents depend on the originator device connecting the K6PM series.
For detailed settings, refer to the manual of the originator device.
• "SYSMAC CS/CJ Series EtherNet/IP Units Operation Manual (Cat. No. W465)"
Device name in hard-
ware list
Unit version
CIP revision
Major revision
Revision name in
hardware list
CJ2B-EIP21
Unit version.2.0 and 2.1
2
Rev2
Unit version.3.0
3
Rev3
CJ2M-EIP21
Unit version.2.0 and 2.1
2
Not available.
CJ1W-EIP21
Unit version.1.0
1
Rev1
Unit version.2.0 and 2.1
2
Rev2
Unit version.3.0
3
Rev3
CJ1W-EIP21
Unit version.1.0
1
Rev1
Unit version.2.0 and 2.1
2
Rev2
Unit version.3.0
3
Rev3
CJ1W-EIP21(CJ2)
*1
*1. This shows the case where the CJ1W-EIP21 Unit is mounted on the CJ2 CPU Unit.
Unit version.2.0 and 2.1
2
Rev2
Unit version.3.0
3
Rev3
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......