Appendices
A - 28
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
3
Creating Network Variables (Input)
Create network variables to be the input area in the PLC.
The Main Unit sends the required tag sets from among the four tag sets (128 bytes, 380 bytes,
380 bytes, and 418 bytes) as input data, therefore the network variable must be created as a
structure variable or an array variable.
This section shows how to create structure variables. (For array variables, the following "(1)
data type registration" are unnecessary.)
(1) Registering Data Type
Create a structure type as a basis by the following procedure to create a structure type net-
work variable (128 bytes, 380 bytes, 380 bytes, or 418 bytes) for receiving the input data of
the Main Unit.
(1)-1 Opening the Data Types Tab Page
Double-click
Data Type
under
Programming
|
Data
in the Multiview Explorer, or right-click
Data Type
and select
Edit
from the menu.
(1)-2 Registering structure Type
Click the
Structures
Side Tab in the Data Type Editor, and then the Structure Data Type
Editor is displayed.
In the Data Type Editor, press the
Insert
Key or right-click and select
Create New Data
Type (N)
, and enter a structure name. As an example, we set "t_K6PM_THM1" to
"t_K6PM_THM4" here. An error is displayed because there is no structure member regis-
tration at this time.
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......