4 Monitoring the Temperature in Control Panel with the Main Unit and the Software Tool
4 - 6
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
Symbol
Name
Description
A
No.
This is the number of the Main Unit. 01 to 05 It cannot be changed (only for this
screen).
B
Name/IP
address
Displays the name and IP address of the Main Unit.
• The default name of the Main Unit is from K6PM_01 to 05 (can be changed), and
can be up to 32 single-byte characters and 16 double-byte characters.
• The IP address of the Main Unit set on the
Setting K6PM
Screen is displayed as the
IP address. During startup, the IP address read from the project file is displayed.
C
Alarm
Comprehensive alarm occurrence (Threshold 1 exceeded or threshold 2 exceeded.)
: Threshold 1 exceeded,
: Threshold 2 exceeded
*1
D
Status
The top three of the following are displayed.
• Any one of during monitoring, during setting, or during interruption
• During monitoring: Registration state
• Setting: Unregistered state
During interruption: During measurement interruption due to the input of an external
trigger
• Communications status with the Main Unit
: Normal, : Error
• K6PM-TH sensor error occurrence state
: Sensor type error,
: Temperature measurement range exceeded,
:
K6PM-TH sensor angle deviation detected,
: K6PM-TH sensor communications
error
E
Switch Sta-
tus
Button
The status of the Main Unit can be switched by any one of the following:
• Setting: The display moves to the
Setting K6PM
Screen.
• Monitoring: The display moves to the
Monitoring K6PM
Screen.
• Stop monitoring: The monitoring of the Main Unit is stopped.
F
Log folder
Button
Place the cursor on this button to view the folders for saving the log file.
Click the button to open the folder for saving the log file in Explorer.
G
System set-
ting
Button
The display moves to the System setting Dialog Box.
The language and sampling cycle can be set.
H
Close
Button
Use this button to exit the
Device List of K6PM
Screen, and view the screen for con-
firming that the project has been saved.
A
B
C
D
E
H
F
G
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......