![background image](http://html1.mh-extra.com/html/omron/k6pm-th/k6pm-th_user-manual_743374120.webp)
5 Monitoring and Setting with the EtherNet/IP Communications
5 - 18
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
Note The contents of the error response code that can occur when the above service codes are executed are as
described below.
Service
code
Service name
Description
Supported services
Classes
Instances
4D hex
Search_Results_Re-
flect
Reflect K6PM-TH sensor search result
Request data
*1
...
1: Reflect sensor search result (0001 hex,
Data type: UINT)
*1. The "K6PM-TH sensor type" in the K6PM-TH sensor status is reflected in the "K6PM-TH sensor type registra-
tion" of the setting object.
An error response (10 hex) is returned when in the monitoring mode and K6PM-TH sensor position adjustment
mode.
Not supported
Supported
4E hex
Sensor_Posi-
tion_Registration
K6PM-TH sensor location registration
Request data
*2
...
1: K6PM-TH sensor 1 location registration,
2: K6PM-TH sensor 2 location registration,
:
31: K6PM-TH sensor 31 location registration
(0001 to 001F hex, Data type: UINT)
*2. An error response (10 hex) is returned when in the monitoring mode.
If position registration is not performed for the target sensor, an error response (0C hex) is returned.
Not supported
Supported
4F hex
Max_Reset
Max. temperature reset
Resets the maximum temperature of all sen-
sors connected to the corresponding Main
Unit.
Request data...
1: Reset the past maximum temperature of all
sensor segments (0001 hex, Data type:
UINT)
Not supported
Supported
Error response code
Error response name
Error contents
0B hex
Already in requested
mode/state
The object is already in the mode or state being
requested by the service.
0C hex
Object state conflict
The object cannot execute the requested service
in its current state.
10 hex
Device state conflict
The device cannot execute the requested service
in the current mode or state.
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......