background image

 

Eco

 

Sensors

   

Ozone

 

Controller,

 

Model

 

OS

6

 

1

 

Division

 

of

 

KWJ

 

Engineering

 

Inc.

  

User

 

Manual,

 

Rev.

 

1.4

 

[email protected]

 

or

 

(800)

 

472

6626

 

USER MANUAL 

 

OZONE SWITCH 

Model OS-6 

 

OS-6 Features 

The  OS-6  is  an  industrial  grade  ozone  controller  and  monitor.  The  OS-6  design  is  optimized  for 
accuracy and ease of installation, setup and operation.  

 

x

  Front panel digital LCD displays ozone level.  

x

  Rugged, splash resistant NEMA 4X enclosure for 

industrial environments.  

x

  Easily  accessible  connection  terminals  and 

controls  allow  the  unit  to  be  setup  after  it  is 
mounted. 

x

  LED  indicators  display  when  ozone  exceeds  the 

0.1  ppm  OSHA  limit  and  a  variety  of  other 
important ozone control parameters. 

x

  Set  points  for  ozone  generator  control  relays  are 

digitally  controlled  with  numeric  set  points.  This 
makes precise ozone control easy to set up, even 
when ozone is not present.  

x

  Ozone  generator  failure  mode  detection  warns  when  the  connected  ozone  generator  is  not 

maintaining the desired ozone set points. This option can be disabled.   

x

  “Monitor Mode”  can  be  enabled on  the  OS-6  panel.  This  mode  disables  the  ozone  generator 

controller and generator failure mode status indicators while maintaining ozone measurement 
and limit warning indicators.  

x

  Analog  outputs  (4-20  mA  and  0-2  VDC)  are  compatible  with  PLCs  and  other  process 

controllers.   

x

  Digital  serial  output (RS-232)  allows  for  convenient  connection  to  a  computer.  Data  output: 

ozone (ppb), temperature (°C), and relative humidity (%).   

Summary of Contents for OS-6

Page 1: ...variety of other important ozone control parameters x Set points for ozone generator control relays are digitally controlled with numeric set points This makes precise ozone control easy to set up eve...

Page 2: ...power analog outputs relay outputs and Monitor Mode selector are located in the Wiring Compartment For access disconnect the OS 6 from power and remove the two screws and cover The connection board w...

Page 3: ...he LCD will display digits Power the OS 6 and connected SM module for 1 hour before response testing Prior to on site process integration operate on power for 24 hours We recommend testing the instrum...

Page 4: ...ached SM module to determine the measurement range The OS 6 is shipped from the factory with the Analog Output Full Scale Range set to match the installed SM module For further details refer to the sp...

Page 5: ...defects in materials and workmanship for one year following the date of purchase by the original owner This warranty does not include damage to the product that results from misuse accident dropping m...

Page 6: ...6 Wiring Compartment Panel SM Module User Replaceable Sensor Connects Here SM Module OS 6 Wiring Compartment Panel Power In GND 12 24 VDC 3 Wire Cable Power Out Data In GND 5VDC WARNING Never connect...

Page 7: ...al SM module Connection A power relay is required if the load exceeds the OS 6 relay ratings Power Relay Analog Outputs to Process Controller Refer to SM Module Wiring Illustrations N O COM N C Genera...