Specification
Section 14-1
Test/Restart Input
10 mA @ 24 VDC, Normally closed input, t
Pulse
>
2,5s
Muting A
10 mA @ 24 VDC
Muting B
10 mA @ 24 VDC
EDM - Monitor Input
max. 6 W => 250 mA @ 24 VDC
Muting Lamp LMS
50 mA min @ 24 VDC (LED and bulb based lamps)
Input pulse characteristic
t
Pulse
< 2xResponse time of the system
Safety Output (OSSDs)
Two PNP safety outputs, each output sourcing
250 mA @ 24 VDC. Short circuit protection
Voltage Drop
< 2.3 V
Leakage current
< 1 mA
Capacitive Load
< 250 nF for OSSD output
Inductive Load
Please contact your Omron representative for further
information.
Test pulse data
t1: Test pulse
300 µs
t2: Test interval > Response time x 0.33
t3: Repetition > Response time x 0.66
Power Supply
Must meet the requirements of EN/IEC60204-1 and
EN/IEC61496-1, and must guarantee safe insulation
from the mains voltage in accordance with IEC60742
and be able to cover a drop of supply voltage of at
least 20 ms.
Protection class (IEC 536 or
VDE 106)
III
Power-on delay
<2 s
Insulation resistance
>20M
Dielectric Voltage Strength
350 VAC (1 min)
Connections
Cable length
F3S-TGR-CL Transmitter
Shielded cables:
Max. 50 m, @ 0.2 mm
2
Max 100 m, @ 0.4 mm
2
Coding connections does not reduce the max cable
length
We recommend to use the F39-TGR-CVL cables
to connect the F3S-TGR-CL system to the
machine control system.
Cable length
F3S-TGR-CL Receiver
Shielded cables:
Max. 50 m, @ 0.2 mm
2
Max 100 m, @ 0.4 mm
2
Coding connections does not reduce the max cable
length
We recommend to use the F39-TGR-CVL cables
to connect the F3S-TGR-CL system to the
machine control system.
Cable length
F3S-TGR-CL-MIX system
Shielded cables, M12 connector 8-pin, these cables
are shipped with the sensors. Maximum length is
0.9 m between segments
Electrical
OSSD1
OSSD2
t
1
t
t
2
t
3