Wiring to two forcibly guided relays
Section 10-4
10-4 Wiring to two forcibly guided relays
F3S-TGR-CL is set in manual reset operation mode.
Note
For Active - Passive systems please keep in mind there is no wiring on Trans-
mitter (Passiv) side.
Note
The achievable safety category or performance level using this circuit
depends on the safety light curtain in use and the correct wiring of the safety
control unit.
Note
This circuit can achieve a PL=e acc. ISO 13849-1 if a F3S-TGR-CL-4_ is
used.
Shield
Mut.
B (Y
ello
w)
+24
VDC (Bro
wn)
OSSD1 (Gr
ay)
Te
st (White)
+24 (Bro
wn)
OSSD2 (Pink)
Te
st/restar
t (White)
0VDC (Blue)
Mut.
A (Green)
Mut.
Lamp (Red)
Shield
0
VDC (Bl
ue)
R
S
T
F3S-TGR-CL
11
23
33
43
44
34
24
12
0
1
11
23
33
43
44
34
24
12
0
1
RESTART
TEST
M
24Vdc +
-
G7SA-3A1B
G7SA-3A1B
RECEIVER
TRANSMITTER