Selecting External Device Monitoring (EDM)
Section 6-2
Firmware 1.3.6
6-2
Selecting External Device Monitoring (EDM)
EDM is activated by setting position 6 of Switches A and B located on the
receiver. Any mismatch between the settings of Switches A and B will result in
an alarm condition.
Switch
Status
Function
8
OFF
Manual reset
ON
Automatic reset
7
OFF master
lower bank
No codification (dip 7 slave useless)
ON master
lower bank
Codification available by dip 7 slave
OFF slave
upper bank
CODE A
ON slave
upper bank
CODE B
6
OFF
EDM function disabled
ON
EDM function enabled
5 + 4
1
1. Selector switches 4 and 5 are operational if a muting indicator is connected or both are set to the ON position
4
5
MUTING and SPECIAL FUNCTIONS
OFF
OFF
MUTING T + t 0,2s deactivation
OFF
ON
MUTING L + t 0,2s deactivation
ON
OFF
MUTING X + t 0,2s deactivation
ON
ON
SPECIAL FUNCTION WITH Switches 1, 2 and 3
MUTING MAPS when MUTING T, L or X are selected on switches 4 and 5
2
2. Selector switches 1, 2 and 3 are operational if a muting function is set and a muting indicator is connected.
3 + 2 + 1
1
2
3
OFF OFF OFF
Muting active over all light curtain
OFF OFF ON
Muting active on module 1,2,3 and 4
OFF ON
OFF Muting active on module 1,2 and 3
OFF ON
ON
Muting active on module 1 and 2
ON
OFF OFF Muting active on module 1
ON
OFF ON
Muting active on module 2
ON
ON
OFF Muting active on module 3
ON
ON
ON
Muting active on module 4
Pre-reset selection or Total muting timing selection when dips 4-5 are both ON
3
3. Selector switches 1, 2 and 3 are operational if selector switches 4 and 5 are in ON position
3 + 2 + 1
1
2
3
OFF OFF OFF Muting type T + t 1s deactivation
OFF OFF ON
Muting type L + t 1s deactivation
OFF ON
OFF Muting type X + t 1s deactivation
OFF ON
ON
Muting type T + no t 1s deactivation
ON
OFF OFF
Muting type L + no t 1s deactivation
ON
OFF ON
Muting type X + no t 1s deactivation
ON
ON
OFF Pre-Reset mode
ON
ON
ON
Muting type X compatible with old wiring and timing
F06E-EN-03A+F3S-TGR-CL_K+OperManual.book Seite 12 Dienstag, 4. Oktober 2011 1:32 13