Partial Muting Configuration
Section 11-2
11-2 Partial Muting Configuration
This function is only available on the F3S-TGR-CL_A - models.
Some applications require a muting function that is not covering
the entire protective field.
The protective field of the F3S-TGR-CL system is build of optical
modules. Each module in a F3S-TGR-CL system can be
addressed individually and carries a number of individual
beams.
The partial muting function allows to select the modules on
which muting is performed.
Note
The module opposite side of the connector can not be used for partial muting.
11-2-1 Setting the partial muting function
Use the selector switches to set the partial muting function:
Note •
If the F3S-TGR-CL system uses more than 4 modules, the partial muting
function is limited to modules 1 to 4.
•
The number of modules is shown in the list of models in the technical data.
11-3 Override
This function is only available on the F3S-TGR-CL_A - models.
This function is a manual triggering of the muting function after an error in the
muting procedure. An error-free state can be established by simulating a valid
muting condition. This allows to clear the protective field by using the override
function.
Typical applications can be found eg. in palletizing machines. If a pallet
stopped in the protective field, the Safety sensor system can not be restarted
without removing the pallet.
!WARNING
Make sure that the operator is able to check the entire protective field as long
as override function is enabled. Failure to do so may result in serious injury.
Note •
To start override, the F3S-TGR-CL must be in MACHINE STOP state.
12
3
4
MUTING MAPS when MUTING T, L or X are selected on switches 4 and 5
*1
*1. Selector switches 1, 2 and 3 are operational if a muting function is set and a muting indicator is connected.
3 + 2 + 1
1
2
3
OFF OFF OFF
Muting active over all light curtain
OFF OFF ON
Muting active on module 1,2,3 and 4
OFF ON
OFF Muting active on module 1,2 and 3
OFF ON
ON
Muting active on module 1 and 2
ON
OFF OFF Muting active on module 1
ON
OFF ON
Muting active on module 2
ON
ON
OFF Muting active on module 3
ON
ON
ON
Muting active on module 4