Receiver Diagnostic information
Section 16-1
16-1-3 LED error indication
Disposition of indicator
Name of indicator
Colour
POWER
Green
STATUS
Yellow
GUARD
Green
BREAK
Red
INTERLOCK
Yellow
Description of Error
Corrective action needed
Low supply voltage
Check if power-supply is within the specification
(24 VDC±20%)
Control logic fault
Remove and reapply power. If the error is still
present, please check the DIP switch settings,
otherwise contact your local Omron distributor
Error in Safety Outputs Check the wiring of the OSSD outputs.
Muting lamp connec-
tion fault of muting
lamp defective
Check the connection of the muting lamp and/or
check the condition of the muting lamp
Mutual light interfer-
ence
Check the presence of ambient light sources
close to the protection field. Use coding option
or remove the light source.
Error in floating blank-
ing mode. Object out-
side the blanking area
or missing fixed blank-
ing object
Check the position of the blanking object. Make
sure it is inside the blanking area.
EDM fault
Check and correct EDM wiring.
Error in pre-reset func-
tion
Pre-reset condition was not met. Correct place-
ment of the pre-reset switch to keep timing
within the specification.