63
Transmitter Diagnostic information
Section 16-2
16-2 Transmitter Diagnostic information
16-2-1 Normal operation
16-2-2 LED error indication
Disposition of indicator
Name of indicator
Colour
POWER
Green
STATUS 1
Yellow
NEAR/FAR
Green
Not used
-
STATUS 2
Yellow
Description
Normal operation, long range selected
Normal operatioin, short range selected
Disposition of indicator
Name of indicator
Colour
POWER
Green
STATUS 1
Yellow
NEAR/FAR
Green
Not used
-
STATUS 2
Yellow
Description of Error
Corrective action needed
Low supply voltage
Check if power-supply is within the specification
(24 VDC±20%)
Control logic fault
Remove and reapply power. If the error is still
present, contact your local Omron distributor
Error on range selec-
tion
Check the setting of the selector switches for the
range selection
POWER
ST
A
TUS 1
NEAR/F
AR
ST
A
TUS 2
TX
POWER
ST
A
TUS 1
NEAR/F
AR
ST
A
TUS 2
TX