Network Installation
Section 3-6
34
CJ-series PLCs
CJ-series FL-net Units can be mounted to either a CJ-series CPU Rack or a
CJ-series Expansion Rack. Mount the Units to any of the positions shown in
the following diagram, and secure with the slider on the top and bottom of the
Unit. Up to four FL-net Units can be mounted to a single PLC. If an FL-net Unit
is mounted in combination with other CPU Bus Units (e.g., Controller Link
Units), the maximum total number of CPU Bus Units that can be mounted is
16.
Note
The current consumption of the CJ1W-FLN22 FL-net Unit is 370 mA maxi-
mum. Make sure that the total current consumption of all Units mounted to the
CPU Rack or Expansion Rack to which the FL-net Unit is mounted does not
exceed the capacity of the Power Supply Unit.
3-6
Network Installation
3-6-1
Basic Installation Precautions
• Take the greatest care when installing the Ethernet System, being sure to
follow ISO 8802-3 specifications. You must obtain a copy of these specifi-
cations and be sure you understand them before attempting to install an
Ethernet System. Unless you are already experienced in installing com-
munications systems, we strongly recommend that you employ a profes-
sional to install your system.
• Do not install Ethernet equipment near sources of noise. If noise-prone
environments are unavoidable, be sure to take adequate measures
against noise interference, such as installing network components in
grounded metal cases, using optical links in the system, etc.
P
S
C
P
U
I
C
P
S
P
S
P
S
I
I
I
I
I
I
End cover
End cover
End cover
End cover
10 Units max.
10 Units max.
10 Units max.
10 Units max.
CPU Rack
Expansion Rack
Expansion Rack
Expansion Rack
Note
PS: Power Supply Unit
CPU: CPU Unit
IC: I/O Control Unit
II: I/O Interface Unit
FL-net Units can be
connected in up to
four of the slots
indicated at the left.
Summary of Contents for CJ1W-FLN22
Page 2: ......
Page 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 14: ...xiv...
Page 18: ...xviii...
Page 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Page 40: ...Precautions Section 1 6 14...
Page 50: ......
Page 88: ...Allocated Words in the DM Area Section 4 4 62...
Page 158: ...Command Response Reference Section 7 5 132...
Page 170: ......
Page 192: ...Inspections Section 10 6 166...
Page 218: ...192 System Configuration Appendix A...
Page 224: ...198 System Configuration Example Appendix B...
Page 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Page 276: ...250 International System of Units Appendix G...