151
Error Log
Section 10-3
0103
Resend count exceeded (send
failed)
Commands
Bit 15:
OFF
Bits 08 to 14: SNA
Bits 00 to 07: SA1
Responses
Bit 15:
ON
Bits 08 to 14: DNA
Bits 00 to 07: DA1
Check transceiver at remote node. ---
0105
Node address setting error (send
failed)
Set the IP address correctly.
---
0107
Remote node not in network (send
failed)
Check the connection to the
remote node.
---
0108
No Unit with specified unit
address (send failed)
Check the unit address at the
remote node.
---
010B
CPU Unit error (send failed)
Troubleshoot the error in the CPU
Unit using the PLC operation
manual.
---
010D
Destination address not in routing
tables (send failed)
Set the destination address in the
routing tables.
---
010E
No routing table entry (send
failed)
Set the local node, remote node,
and relay nodes in the routing
tables.
---
010F
Routing table error (send failed)
Create the routing tables correctly. ---
0110
Too many relay points (send
failed)
Reconstruct the network or cor-
rect the routing tables so that
commands are sent to within a 3-
level network range.
---
0111
Command too long (send failed)
Check the command format and
set the correct command data.
---
0112
Header error (send failed)
Check the command format and
set the correct command data.
---
0117
Internal buffers full; packet dis-
carded
Change the network so that traffic
is not concentrated.
---
0118
Illegal packet discarded
Check for nodes sending illegal
packets.
---
0119
Local node busy (send failed)
Change the network so that traffic
is not concentrated.
---
0120
Unexpected routing error
Check the routing tables.
---
0121
No setting in IP address table;
packet discarded
Set the remote node in the IP
address table.
---
0122
Service not supported in current
mode; packet discarded
Select the IP address table or
both methods for the address con-
version method.
---
0123
Internal send buffer full; packet
discarded
Change the network so that traffic
is not concentrated.
---
0124
Maximum frame size exceeded;
routing failed
Reduce the size of the FINS mes-
sage.
---
021A
Logic error in setting table
00
01: Data link
table
02: Network
parameters
03: Routing
tables
04: Setup
05: CPU Bus
Unit Words
(CIO/DM)
Recreate the data specified by the
2nd byte of the detailed error
code.
Saved
Error
code
Meaning
Detailed error code
Correction
EE-
PROM
1st byte
2nd byte
Summary of Contents for CJ1W-FLN22
Page 2: ......
Page 3: ...CS1W FLN22 100Base TX CJ1W FLN22 100Base TX FL net Units Operation Manual Revised October 2010...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 14: ...xiv...
Page 18: ...xviii...
Page 26: ...xxvi Unit Versions of CS CJ series FL net Units 7...
Page 40: ...Precautions Section 1 6 14...
Page 50: ......
Page 88: ...Allocated Words in the DM Area Section 4 4 62...
Page 158: ...Command Response Reference Section 7 5 132...
Page 170: ......
Page 192: ...Inspections Section 10 6 166...
Page 218: ...192 System Configuration Appendix A...
Page 224: ...198 System Configuration Example Appendix B...
Page 270: ...244 FL net Unit Support Software Ver 1 6 Appendix F...
Page 276: ...250 International System of Units Appendix G...