Assigning Ground-Fault Alarm and Trip Levels
The Setup|G.F. window allows you to set the alarm and trip levels.
Fig. 3.35
Setup|G.F. window (Pipe Freeze Line Control)
Input the Ground-Fault Alarm and Ground-Fault Trip:
Ground-Fault Alarm:
When the ground-fault current exceeds this level the ACS-UIT2 goes in alarm.
Range:
10–200 mA
Default:
20 mA
Ground-Fault Trip:
When the ground-fault current exceeds this level the ACS-PCM2-5 turns off the
circuit relay.
Range:
10–200 mA
Default:
30 mA
Assigning Circuit Voltage
The Setup|Voltage window allows you to set the circuit voltage used to calculate the energy
consumption of the circuit.
Fig. 3.36
Setup|Voltage (Pipe Freeze Line Control)
INPUT THE CIRCUIT VOLTAGE
Voltage: 120, 208, 240 or 277 V (Standard ACS-PCM2-5 panels) Since the C910-485
measures line voltage, this field does not appear.
Default:
208 V