nVent.com
|
93
Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
Power Cycle Start Time:
The time of day to start the Power Cycle test
Range:
00:00 to 23:59
Default:
Each circuit is assigned a unique default start time calculated from the device
address and relay number.
Power Cycle Test Interval:
The frequency to run the Power Cycle Test
Range:
Never, Daily, Weekly and Monthly
Default: Never
3.7. GREASY WASTE AND TEMPERATURE MAINTENANCE MODE
The Greasy Waste control mode prompts you to enter the control parameters for a Greasy Waste
application and other applications with a maintain temperature greater than 70°F.
Note:
Greasy waste mode is also used for XL-Trace applications where line control above 40°F is
required.
Fig. 3.66
Setup|Greasy Waste/TM window
Temperature Setpoint:
The pipe temperature setpoint is the desired maintain temperature. Based
on the measured control temperature, the ACS-UIT2 will switch the relay output to maintain the
system at the desired setpoint.
Range:
70°F (21°C)–140°F (60°C)
Default:
110ºF (43°C)
Economy Temperature (optional):
This value represents the temperature that you want the pipe
to maintain when in economy mode. This input is only accessible if the Setpoint Mode is set to
Variable
which applies the temperature setpoint 24/7 scheduler function described in Appendix 5.2
24/7 Scheduler on page 127.
Enter the Economy Temperature
Range:
70°F (21°C) to Maintain temperature
Default: 90°F (32°C)