Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
parameters embedded in the software to simplify assigning heating cable circuits. The application
designs and assumptions are detailed in their associated design guides and installation manuals
which can be found on www.nVent.com.
The control mode functions programmed in the ACS-30 for each application are summarized in
Table 1.1. These control modes will be discussed in more detail in the configuration section of this
programming guide.
TABLE 1.1 ACS-30: HEATING CABLE APPLICATION PROGRAMMING SUMMARY
CONTROL MODE FUNCTIONS
APPLICATION
NVENT RAYCHEM
HEATING CABLE
CONTROL MODE
CONTROL SETPOINTS
Hot Water Temperature
Maintenance
•
HWAT
•
Preset power duty cycle
•
(HWAT Design Wizard)
•
Constant temp
•
Variable schedule
- Maintain
- Economy
- Off
- Heat Cycle (R2 only)
Floor Heating
•
RaySol
•
MI heating cable
•
Floor sensing
•
Constant temp
•
Variable schedule
- Maintain
- Economy
- Off
•
Circuit override through
RTD or external device
Greasy Waste Disposal and
Temperature Maintenance
•
XL-Trace
•
Line sensing
•
Constant temp
•
Variable schedule
- Maintain
- Economy
- Off
Pipe Freeze Protection
•
XL-Trace
•
Ambient, PASC or
line sensing
•
Constant temp
•
Circuit override through
external device
Fuel Oil Flow Maintenance
•
XL-Trace
•
Ambient, PASC or line
sensing
•
Constant temp
•
Circuit override through
RTD or external device
Freezer Frost Heave Prevention
•
RaySol
•
MI heating cable
•
Floor sensing
•
Constant temp
•
Variable schedule
- Maint
Surface Snow Melting
•
ElectroMelt
•
MI Heating Cable
•
Ambient or surface temp
•
Constant temp
•
External controller
•
External snow controller
Roof & Gutter De-icing
•
IceStop
•
MI Heating Cable
•
Ambient or surface temp
•
Constant temp
•
External controller
•
External snow controller
Temperature Monitor Only
Five temperature monitor only channels
Low and high temperature alarms
Variable Schedule
Setpoint calendar with:
•
7 days/week calendar
•
48 1/2-hr time blocks/day
•
Daily schedule copy function