To add a new device (ACS-PCM2-5, C910-485 or RMM2), make sure it:
•
Has a unique address
•
Has power
•
Is connected to the RS-485 wiring
Then push Update Network to add the device to the list.
Note:
Removal of Device: If you remove a device or RTD from the network, using the Update
Network button will not remove the device from memory. You must use the Remove Device button
found in the Network|Remove window.
Table 2.1 below shows the available device addresses for Relay Outputs and RTDs. If RMM2(s).
They must NOT share the same address as the ACS-PCM2-5 (ACS-CRM) or the C910-485.
TABLE 2.1 AVAILABLE DEVICE ADDRESSES
DEVICE
DEVICE TYPE
SWITCH SETTING
DEVICE ADDRESS
ACS-PCM2-5,
C910-485
Relay Output/RTD
1–99
1–99
RMM2
RTD
0-9
32-41
RMM2
RTD
A-F
42-47
2.1.4.
MAIN WINDOW
After the first system scan has been completed, tap the Main menu button and the main window
appears.
Fig. 2.8
Main window with one CRM board detected
The Main menu window displays the status of all circuits (relays) that are available in the connected
system. In addition to all the available circuits that are assigned to ACS-PCM2-5/C910-485 relays
there are 5 Monitor Only circuits available (TM-A through TM-E). The monitor only circuits are not
assigned to any relays in the ACS-PCM2-5 panels and do not require any additional hardware.
The circuits may be accessed from this window by tapping anywhere on the row for the desired
circuit. If the circuit is unassigned, tapping on the row will allow you to set the control mode and
parameters. If it is already assigned, tapping the row will allow you to edit the control mode and
parameters.
Tap anywhere on the row for the circuit you wish to set up.