ASSIGNING RTDS
In this mode you have the option of setting up to four RTDs with the ACS-PCM2-5, or 2 RTD's
with the C910-485, for slab sensing. For detailed information on the Setup|RTD window, see 2.2.3
Assigning and Sharing RTD Control and Monitoring on page 30.
Fig. 3.13
Setup|RTDs window (Frost Heave)
ASSIGNING TEMPERATURE ALARMS
Once RTDs have been assigned to the circuit the alarm button appears then high and low
temperature alarms may be set.
Fig. 3.14
Setup|Alarms window (Frost Heave)
HIGH LINE TEMP ALARM:
If any RTDs assigned to a circuit measures a temperature above this threshold, the ACS-UIT2
generates an alarm. The limit can be set for any temperature value you desire for your application
within the range allowed.
Range:
Maintain setpoint plus 5°F (3°C) to 90ºF (32°C)
Default:
90°F (32°C)
LOW LINE TEMP ALARM:
If any RTDs assigned to a circuit measures a temperature below this threshold, the ACS-UIT2
generates an alarm.
Range:
0ºF (-18ºC) to Maintain setpoint
Default:
35°F (2°C)