nVent.com
|
39
Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
2.8. EVENTS WINDOW
The Events window displays a chronological history of all events and alarms. It retains the most
recent 2000 entries; after 2000 entries are recorded, the oldest entries are discarded as new entries
are added.
Fig. 2.39
Events window
The Events status listing window provides the following information:
Time
By taping the Time column heading, the display of times of the
events or alarms changes to descending or ascending order based
on time of occurrence.
Circuit
By taping the circuit heading, the display of events or alarms
is sorted by the circuit number. Circuits are first displayed
in ascending order. Taping the circuit again toggles between
ascending or descending order.
Events, Press for Alarms
By taping the Events heading, the Events display filters events or
alarms by type. Time and Circuit column headings can then be
used to further sort the selected events or alarms for display.
Note:
The program automatically skips an alarm type if no alarms
of that type exist).
TABLE 2.4 ALARM TYPE HEADINGS AND DESCRIPTIONS
ALARM TYPE/
HEADINGS
DESCRIPTION
Comm Alarm
ACS-UIT2 display lost communication with an ACS-PCM, C910-485
and/or RMM2 device(s).
Fail Safe Alarm
Control mode of circuit has been switched to Fail Safe control mode.
Ground-Fault Alarm
Heating cable’s ground-fault current went above high ground-fault
current alarm setting.
Ground-Fault Trip
Heating cable’s ground-fault current went above the ground-fault trip
setting.
High Temp
RTD temperature went above high temp alarm setting.
High Temp Cut-Out
RTD temperature went above high temp cut-out alarm setting.