Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
3.5.2.
TEMP CONTROL – LINE CONTROL
Fig. 3.31
Pipe Freeze Temperature Line Control window
The Temp Control window allows you to select the temperature control mode to Ambient Control,
Line Control or PASC. This option depends on where the controlling RTD inputs are situated and
utilized: either measuring the temperature of the environment surrounding the pipe (ambient), or
directly on the pipe itself (line). Tap: Line
Fig. 3.32
Setup|Pipe Freeze Line Control window
Setpoint Temperature:
The setpoint temperature is the desired maintain temperature for the
water pipe.
Based on the measured control temperature, the ACS-PCM2-5 will switch the relay output to
maintain the system at the desired setpoint.
Range:
35°F (2°C)–50ºF (10°C)
Default:
40ºF (4°C)
Deadband:
If the control temperature is above the setpoint temperature plus deadband, the relay
output is turned off. If the control temperature is below the setpoint temperature, the output is
turned on.
Range:
1°F (1°C)–10°F (6°C)
Default:
5ºF (3°C)