Assigning Ground-Fault Alarm and Trip Levels
The Setup|G.F. window allows you to set the alarm and trip levels. Tap the G.F. button to access the
Setup|G.F. window.
Fig. 3.87
Setup|G.F. Window (Roof & Gutter - Bracketed Ambient Temp Control)
Input the Ground-Fault Alarm and Ground-Fault Trip:
Ground-Fault Alarm:
When the ground-fault current exceeds this level the ACS-UIT2 goes in alarm.
Range:
10–200 mA
Default:
20 mA
Ground-Fault Trip:
When the ground-fault current exceeds this level the ACS-PCM2-5, or C910-485,
turns off the circuit relay.
Range:
10–200 mA
Default:
30 mA
Assigning Circuit Voltage
The Setup|Voltage window allows you to set the circuit voltage used to calculate the energy
consumption of the circuit.
Fig. 3.88
Setup|Voltage Window (Roof & Gutter - Bracketed Ambient Temp Control)