1.4. USER RESPONSIBILITIES
The performance, reliability and safety of your heating cable system depend on proper design,
selection, and installation. The ACS-30 Software will help you configure and monitor a system that
meets your requirements, but it is only a tool. It assumes that your input is accurate, that you are
familiar with heating system design and configuration, and that you will ensure that all components
of the heating system are installed, maintained and used as intended. The configuration of the ACS-
30 Software should be reviewed by a knowledgeable engineer to ensure it is appropriate for your
application. Additional information relating to safety, design, and installation is contained in Design
Guides, Installation Manuals, Data Sheets, and other literature available from nVent. Be sure to
consult these documents as needed.
1.5. SAFETY WARNINGS
There are important safety warnings shipped with nVent products and printed in the ACS-UIT2
Installation Instructions (H58661), the ACS-PCM2-5 Installation Instructions (H58672) and in
the ACS-30 Program Integrator User Manual (H58325). Be sure to read and follow these safety
warnings to reduce the risk of fire, shock, or personal injury. If you have any questions, contact your
local representative or contact nVent directly.
1.6. TECHNICAL SUPPORT
For technical support, contact your local representative, or contact nVent directly:
NVENT THERMAL MANAGEMENT
Tel: 800.545.6258
Tel: 650.216.1526 (outside U.S.)
Fax: 800.527.5703
Fax: 650.474.7711
email: [email protected]
1.7. STARTING THE ACS-30
1.7.1.
INITIAL SETUP
The ACS-30 software is designed to run only on the ACS-UIT2 hardware platform. Prior to shipment,
the ACS-30 software is installed into a nonvolatile area of the ACS-UIT2 memory. During the initial
power-up, you will see a blue background “splash” window for approximately 30 seconds as the
system software is loaded and initializes.
This V7.0.X program update is compatible only with the ACS-UIT2 User Interface Terminal but
will support both ACS-PCM-5 and ACS-PCM2-5 power control modules as well as the C910-485
controller.
1.7.2.
SYSTEM REQUIREMENTS
The minimum configuration to use the ACS-30 software is:
•
ACS-UIT2
•
At least one ACS-PCM2-5
Maximum equipment configuration:
•
The ACS-UIT2 can control up to 260 circuits. Each ACS-PCM2-5 handles 5 circuits and
the C910-485 is a single circuit controller. There are 99 address that can be assigned to
ACS-PCM2-5 control panels, C910-485 controllers and RMM2.
•
Up to 16 RMM2 (8 channel RTD multiplexing hubs)
1.8. CONTROL MODE MATRIX
The ACS-30 is designed for nVent commercial heating cable systems and their applications. The
programming is focused on eight heating cable applications, and a monitor only mode, with control