To enter an IP address and Subnet Mask manually, click on the IP Address tab, select “Specify an IP
Address,” enter the IP Address, the Subnet Mask, and Default Gateway.
Note:
The set-up parameters above should be provided by your network administrator. The “Name
Server” tab is not applicable for this application.
Modbus Address
Each ACS-UIT2 must have a unique Modbus address which is set by you. The BMS or host
computer can communicate with up to 247 separate ACS-UIT2 units by using Modbus protocol.
Range: 1–247
Default: 1
Baud Rate
Allows you to select the baud rate of the external communication port.
Selection: 2400, 4800, 9600, 19200, 38400, 57600
Default: 9600
Serial Port Mode
This activates a window which allows selection of RS-232 or RS-485 ports. This selects the serial
communication mode for the host port.
Selection: RS-232, RS-485
Default: RS-485
Transmit Delay
This sets the time the ACS-UIT2 will wait after it receives a message before it replies.
Range:
0–5000 milliseconds
Default: 0
Receive Timeout
This sets the time the ACS-UIT2 waits after last character is received before it determines that the
message has ended.
Range:
0–1000 milliseconds
Default: 50
Read/Write Port
Defines which communication protocol (i.e. serial or Ethernet) has BOTH read and write data
access capabilities. By default, the communication medium NOT selected has read-only data
access capabilities.
Options: Serial, Ethernet
Default: Serial