2.2. SETUP WINDOW
The Setup window is displayed after tapping the circuit on the Main window you wish to configure,
or by tapping the Setup button on the Main menu at the top of the window.
Fig. 2.9
Setup window for unassigned circuit
2.2.1.
ASSIGNING CIRCUIT IDENTIFICATION
In this window you will be assigning an ACS-PCM2-5 address and relay number or Temp Monitor
address and providing a name for your circuit.
SETUP WINDOW FIELDS
Address Toggle Button:
This button toggles between the PCM Address and the Temperature Channel.
PCM Address:
Displays the ACS-PCM2-5/C910-485 address that was detected from the network
scan. If you enter the Setup screen without selecting a PCM (circuit), the first PCM-relay detected
in your network will be displayed. You may enter the desired PCM and relay number on the setup
window to configure the circuit.
Relay Number:
The circuit # label is assigned when scanning the network with the ACS-30 program.
By default each of the five relays are numbered as the CRM number and relay number (e.g. 1-1, 1-2,
1-3, 1-4 and 1-5). The CRM number and relay number are a primary reference for all windows. Once
a circuit is added, you cannot delete it or change its PCM number. To remove the entire PCM, you
must go to the Network|Remove window.
Temp Monitor:
Displays an entry field to configure a temperature monitor only channel. Tap the
entry field and select the temperature monitor channel (TM-A to TM-E) you wish to configure. Refer
to Section 4 Temperature Monitor Only Circuits on page 124 for specifics.
ID:
A user defined circuit identification text field. The default is “ID X-X” (where X-X is the Circuit
number). Before the circuit is assigned the ID tag is set as “unassigned.”
When selected, a text-editing window appears that works similar to cell phone text messaging.
There are selection keys for uppercase letters, lowercase letters, and special characters. The keypad
portion allows you to enter text by pushing the appropriate keys.
Limit: 40 characters (character strings are truncated on the Main window after 16 characters but
displayed in full on Status and Setup windows)