nVent.com
|
96
Raychem-AR-H58692-ACS30UIT2Programming-EN-1805
ASSIGNING GROUND-FAULT ALARM AND TRIP LEVELS
The Ground-fault window allows you to set the alarm and trip levels. Tap the G.F. button to access
the ground-fault window.
Fig. 3.69
Setup|G.F. window (Grease/TM Waste)
Input the Ground-Fault Alarm and Ground-Fault Trip:
Ground-Fault Alarm:
When the ground-fault current exceeds this level the ACS-UIT2 goes in alarm.
Range:
10–200 mA
Default:
20 mA
Ground-Fault Trip:
When the ground-fault current exceeds this level the ACS-PCM2-5, or C910-485,
turns off the circuit relay.
Range:
10–200 mA
Default:
30 mA
Assigning Circuit Voltage
The Setup|Voltage window allows you to set the circuit voltage used to calculate the energy
consumption of the circuit.
Fig. 3.70
Setup|Voltage window (Grease/TM)