ASSIGNING POWER CYCLE TEST
The Setup|Maint. window allows you to enable the Power Cycle test start time and frequency. After
the start time and frequency are entered the time of the next test will be displayed on this screen.
Note:
If the circuit is disabled, forced on, or forced off, the power cycle test will be disabled until the
circuit is enabled.
Fig. 3.37 Set
up|Maint. (Pipe Freeze Line Control)
Input the start time and frequency for the Power Cycle test:
Power Cycle Start Time:
THE TIME OF DAY TO START THE POWER CYCLE TEST
Range:
00:00 to 23:59
Default:
Each circuit is assigned a unique default start time calculated from the device
address and relay number.
Power Cycle Test Interval:
THE FREQUENCY TO RUN THE POWER CYCLE TEST
Range:
Never, Daily, Weekly and Monthly
Default: Never
3.5.3.
TEMP CONTROL – PASC CONTROL
Fig. 3.38
Pipe Freeze Temperature PASC Control window