HIGH LINE TEMP CUT-OUT ENABLE/DISABLE:
Enables or disables the high line cut-out capability. When enabled, the ACS-UIT2 alarms and the
output relay turns OFF if any RTDs exceeds the cut-out value for the alarm filter time period. If the
high line temp cut-out is disabled, the relay output will continue to function normally without the
high temperature cut-out feature.
Options: Enable or Disable
Default: Enable
Assigning Ground-Fault Alarm and Trip Levels
The Setup|G.F. window allows you to set the alarm and trip levels.
Fig. 3.11
Setup|G.F. window (HWAT)
Input the Ground-Fault Alarm and Ground-Fault Trip:
GROUND-FAULT ALARM:
When the ground-fault current exceeds this level the ACS-UIT2 goes in alarm.
Range:
10–200 mA
Default:
20 mA
GROUND-FAULT TRIP:
When the ground-fault current exceeds this level the ACS-PCM2-5 or C910-485 turns off the
circuit relay.
Range:
10–200 mA
Default:
30 mA