9 Operation
Maschinenfabrik Reinhausen GmbH 2021
68
7817454/02 EN
TAPCON
®
230 Expert
Setting
Description
Hardware only
The device accepts commands through digital inputs.
SCADA only
The device accepts commands via SCADA.
Hardware and SCADA
The device accepts commands via digital inputs and
SCADA.
Table 13: Selecting remote behavior
9.1.1.2 Set up automatic logout
You can change the settings so that the device of a logged-in user automati-
cally logs the user out after a certain period of inactivity.
These settings apply to all users. If you have activated the Auto login func-
tion for a user, then this user will not be automatically logged out.
1. Go to
Settings > Parameters > System > General
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Auto logout
You can use this parameter to activate th automatic logout function.
Time until auto logout
You can use this parameter to set the time period of inactivity after which a
user is automatically logged out.
9.1.1.3 Activating/deactivating service user access
The device is equipped with user access for the Maschinenfabrik Rein-
hausen GmbH Technical Service department. This access is for error diag-
nostics and troubleshooting in the event of device faults.
You can use this parameter to activate or deactivate service user access. To
safeguard IT security, only activate service user access for a limited time pe-
riod for remedying faults.
If you deactivate the service user access and lose your password for the ad-
ministrator role, it is not possible to reset the administrator password. If the
administrator password is lost, the device must be reset to the default set-
tings. When doing so, all information stored on the device (parameters,
measured values, etc.) will be lost.
You must be assigned the administrator role to set parameters.