8 Commissioning
Maschinenfabrik Reinhausen GmbH 2021
66
7817454/02 EN
TAPCON
®
230 Expert
8. Press
on the follower to select auto mode.
ð
The follower switches to the same tap position as the master.
9. Press
on the master to select auto mode.
10. Press
on the follower to select manual mode.
11. Press
or
on the follower to manually change the tap posi-
tion.
ð
After expiry of the set delay time for parallel operation errors, there is
a tap difference from the follower to the master.
12. Press
several times on the follower to manually increase the tap
position by the number of permitted steps ("Maximum permitted tap dif-
ference") and then one further step.
ð
After expiry of the set delay time for parallel operation errors, there is
a tap difference to follower on the master.
ð
After expiry of the set delay time for parallel operation errors, there is
a tap difference to master on the follower.
13. Press
on the follower to select auto mode.
ð
There is no response. All devices remain blocked.
14. Press
on the master and follower to select manual mode.
15. Press
or
on the master and follower to manually set the
desired step.
ð
The function tests for the tap synchronization method are complete.
Installation and commissioning of the device is complete.