![MR TAPCON 230 AVT Operating Instructions Manual Download Page 153](http://html.mh-extra.com/html/mr/tapcon-230-avt/tapcon-230-avt_operating-instructions-manual_1844351153.webp)
13 Technical data
Maschinenfabrik Reinhausen GmbH 2021
153
7817454/02 EN
TAPCON
®
230 Expert
10
20
30
40
50
100
V
300
0.1
0.2
0.5
1
2
5
10
20
A
U
I
Figure 61: Contact load capacity of digital outputs with resistive load
CAUTION
Electric shock!
The outputs of the DO assembly have plug-based electrical isolation. A mix-
ture of voltage ranges (e.g. extra low voltage and low voltage) or various
phases within a plug can lower the protection against electric shock.
► Use the same voltage ranges within a plug.
► Use the same phase within a plug.
Interface
Pin
Description
1
2
3
4
4
Common reference (common) output 1
3
Common reference (common) output 0
2
Output 1
1
Output 0
Table 68: Connector X1 (group 0)
Interface
Pin
Description
1
2
3
4
4
Common reference (common) output 3
3
Common reference (common) output 2
2
Output 3
1
Output 2