![MR TAPCON 230 AVT Operating Instructions Manual Download Page 126](http://html.mh-extra.com/html/mr/tapcon-230-avt/tapcon-230-avt_operating-instructions-manual_1844351126.webp)
9 Operation
Maschinenfabrik Reinhausen GmbH 2021
126
7817454/02 EN
TAPCON
®
230 Expert
Only change the parallel operation method when the on-load tap-changers
are not performing tap-change operations.
Option
Description
Master
The device is designated as
the master.
Tap synchronization parallel
operation method
Follower
The device is designated as
the follower.
Auto. tap sync.
Automatic assignment of
master or follower.
If a master is not detected,
the device with the lowest
CAN bus address is auto-
matically designated as the
master. All other devices are
designated as followers.
Circulating reactive
current
Circulating reactive current minimization with CAN bus
communication parallel operation method
Power factor
Circulating reactive current minimization without CAN bus
communication parallel operation method
Table 43: Setting parallel operation method
9.3.3.2.3 Assigning a CAN bus address
You can use this parameter to assign a CAN bus address to the device. So
that all devices can communicate using the CAN bus, each device requires a
unique identifier. If the value is set to 0, then no communication takes place.
9.3.3.2.4 Setting circulating reactive current sensitivity
You can use this parameter to set the influence of circulating reactive current
on how the control deviation is calculated. The higher the set value, the
greater the calculated control deviation as a result of circulating reactive cur-
rent.
To determine the ideal circulating reactive current sensitivity, note the rele-
vant section in the Commissioning chapter.
9.3.3.2.5 Setting the circulating reactive current blocking limit
You can use this parameter to set the limit value for the maximum permissi-
ble circulating reactive current. This value is based on the rated current of
the current transformer. If, during parallel operation, the circulating reactive
current exceeds the set limit value, the device triggers the
Circulating reac-
tive current blocking limit exceeded
event. All devices operating in the paral-
lel operation group are blocked.