4 Product description
Maschinenfabrik Reinhausen GmbH 2021
21
7817454/02 EN
TAPCON
®
230 Expert
– Reactive power monitoring
– Power factor monitoring
▪ Display of all measured values such as voltage, current, active power, ap-
parent power and reactive power
▪ Tap position capture
– Via BCD code
– Via dual code
– Via gray code
– Via resistor contact series
– Via N/O contact series
– Analog
▪ Parallel operation of up to 16 transformers in 2 groups using the following
methods:
– Master (tap synchronization)
– Follower (tap synchronization)
– Automatic tap synchronization
– Circulating reactive current
– Power factor
▪ SCADA
– IEC 60870-5-101
– IEC 60870-5-104
– IEC 61850 Edition 2
– Modbus RTU
– Modbus TCP
– DNP3
4.4 Operating modes
Auto mode (AVR AUTO)
In auto mode, the device automatically regulates the voltage in accordance
with the set parameters. It is not possible to perform manual tap-change op-
erations using operating controls or inputs.
Manual mode (AVR MANUAL)
In manual mode, you can perform manual tap-change operations to increase
or decrease the voltage. There is no automatic voltage regulation.
Local mode (LOCAL)
In local mode, you can make entries and issue commands using the device's
operating controls. You cannot use inputs to make entries or issue com-
mands.